Control systems
First-order system and time constant
Also called: first-order lag · time constant · τ · exponential approach
Definition
A first-order system responds to a step by approaching its new value exponentially; its time constant τ is the time to cover 63.2 % of the change.
Picture it
Heating a room, spinning up a motor against friction, charging a capacitor: each slows down as it nears the target, because the driving difference shrinks. Every τ removes 63.2 % of what is left. After about 4τ it is within 2 %.
The maths
τ dy/dt + y = K u step response: y(t) = K u (1 − e^(−t/τ))
| Quantity | Unit | Symbol |
|---|---|---|
| time | second | s |
| ratio | dimensionless | 1 |
Worked example
A motor's speed responds as a first-order system with τ = 0.25 s and final speed 200 rad/s. What speed is reached after 0.5 s?
- y(0.5) = 200 × (1 − e^(−0.5/0.25)) = 200 × (1 − e^−2)
- = 200 × 0.8647 = 172.9 rad/s
AnswerAbout 172.9 rad/s.
✓ The number in this answer is recomputed from scratch by an automated test.
tune it
PID step response
Simplified model: plant τ·dy/dt = −y + u with τ = 0.5 s and gain 1, forward-Euler steps of 0.01 s, derivative on measurement. Real plants add delay, noise and saturation.
Common misconceptions
- Misconception: A first-order system never overshoots a step; if yours does, it is not first-order.
- Misconception: τ is not the time to finish; it is the time to get 63 % of the way.