A building-sized computer whose hardest problem is getting the heat out.

A data centre is thousands of servers in rows of racks, fed by power that must never stop and cooled by air or liquid that must never fail. Almost every watt the servers use ends up as heat, so the building is really a power plant and a cooling plant wrapped around a computer.

  • 8 components
  • 2 worked equations
  • 1 live model
  • 2 safe experiments

1Exploded view

Take the data centre apart.

plate 10 · data centre, isometric, exploded

Tab to a numbered part (or tap it) to jump to its description. The same parts as a list:

  1. 1Raised floor
  2. 2Rack row A
  3. 3Rack row B
  4. 4Aisle containment
  5. 5Server
  6. 6Cooling unit
  7. 7UPS batteries
  8. 8Chiller

2Major components

What every part does, and how.

  1. 01

    Raised floor

    A floor of removable tiles with space underneath for cold air and cables.

    how →Perforated tiles in front of the racks release cold air exactly where the servers draw it in.

  2. 02

    Rack row A

    Racks of servers, all facing the same way, drawing cold air from the front.

    how →Servers are arranged so their fronts face a cold aisle and their backs face a hot aisle.

  3. 03

    Rack row B

    The facing row, sharing the same contained aisle.

    how →Two rows back to back share one hot aisle that can be enclosed and ducted.

  4. 04

    Aisle containment

    A roof and doors over one aisle so hot and cold air do not mix.

    how →Mixing wastes cooling: cold air that bypasses the servers does no useful work.

  5. 05

    Server

    Processors, memory, storage and network in one tray; fans pull air through it.

    how →A server may draw hundreds of watts; a full rack, many kilowatts.

  6. 06

    Cooling unit

    Fans push warm room air over coils carrying chilled water, then back under the floor.

    how →Heat moves from air to water through finned coils; the water carries it to chillers or cooling towers outside.

  7. 07

    UPS batteries

    Batteries that carry the load for the seconds to minutes until generators start.

    how →An uninterruptible power supply sits between grid and servers so a grid fault is never seen by the computers.

  8. 08

    Chiller

    Outside plant that rejects the collected heat to the air.

    how →A heat pump works against the temperature difference; in cool climates, outside air can do much of the job for free.

3System relationships

Where the energy and information go.

Each block is a part (or the world outside). Solid lines carry energy, dashed lines carry information, dotted lines carry matter such as water or air.

Grid supplyUPSbatteriesRack rowspower + networkFacing rowServersIT loadNetwork usersHot aislecontainedCooling unitair → waterChillerheat → outdoorsUnderfloorcold supply air
Energy (solid)Information (dashed)Matter (dotted) Source Decide Convert Store Output

Flows, in order

  • Grid supply sends energy to UPSenergy: power
  • UPS sends energy to Rack rowsenergy: clean power
  • Rack rows sends energy to Serversenergy: power
  • UPS sends energy to Facing rowenergy: clean power
  • Servers sends information to Network usersinformation: data
  • Servers sends energy to Hot aisleenergy: heat in air
  • Facing row sends energy to Hot aisleenergy: heat in air
  • Hot aisle sends energy to Cooling unitenergy: warm air
  • Cooling unit sends energy to Chillerenergy: warm water
  • Cooling unit sends matter to Underfloormatter: cold air

Loops that close

  • Underfloor feeds back to Serversmatter: cold air

4Physical principles

The physics doing the work.

5Mathematical foundations

The equations, with real numbers in them.

Power usage effectiveness

P_total = PUE · P_IT, E_year = P_total · 8760 h

PUE
total facility power ÷ IT power [–]
P_IT
power drawn by the computers [kW]
E_year
energy per year [MWh]

Worked example

  1. 1.P_total = 1.4 × 500 = 700 kW (200 kW is overhead)
  2. 2.E_year = 700 × 8760 = 6 132 000 kWh = 6132 MWh
Facility power
700 kW
Energy per year
6,132 MWh

AssumesA constant load all year. PUE 1.0 would mean zero overhead; real values are above that.

Air needed to carry the heat

V̇ = P / (ρ · c_p · ΔT)

V̇
volume flow of air [m³/s]
P
heat load [W]
ρ
air density [kg/m³]
c_p
specific heat of air [J/(kg·K)]
ΔT
air temperature rise through the servers [K]

Worked example

  1. 1.ρ · c_p · ΔT = 1.2 × 1005 × 12 = 14 472 J/(m³)
  2. 2.V̇ = 500 000 / 14 472 ≈ 34.5 m³/s
Air flow
34.5 m³/s

AssumesAll heat leaves in the air stream, with no leakage or mixing between aisles.

6Computing architecture

The computer inside the system.

Thousands of servers networked into clusters, with software spreading work across them and moving it away from failures.

  1. Layer 1

    Servers

    Processors, memory and accelerators in racks.

  2. Layer 2

    Network

    Switches at the top of each rack, linked into a fabric across the hall.

  3. Layer 3

    Orchestration

    Schedulers place jobs on machines and restart them elsewhere when hardware fails.

7Engineering trade-offs

Every choice costs something.

  • Run the cold aisle warmer

    Gain:Chillers work less, and more hours of free outside-air cooling.

    Cost:Less margin if a cooling unit fails; some hardware has limits.

  • Liquid cooling to the chip

    Gain:Handles far denser racks; water carries far more heat per volume than air.

    Cost:Plumbing in the racks, leak risk, and more complex maintenance.

  • 2N power redundancy

    Gain:Survives the loss of a whole power path.

    Cost:Roughly double the electrical equipment.

8 · Try it · runs in your browser

Cool the hall

Set the IT load, PUE and the air temperature rise. See the facility power, yearly energy and how much air must move.

500 kW
1.40
12.0 K
Facility power
700 kW
Overhead (cooling, losses)
200 kW
Energy per year
6,132 MWh
Air flow needed
34.5 m³/s

Typical modern efficiency.

82.90.0520Air temperature rise (K)m³/s

ModelConstant load all year; all IT heat leaves in the air stream (ρ = 1.2 kg/m³, c_p = 1005 J/(kg·K)).

9Suggested safe experiments

Things to try, safely.

Every experiment here is virtual or a household-safe observation. Never open real devices, batteries or power supplies, never work on mains electricity, and never look at the Sun.

  1. Observation

    Feel a laptop's airflow

    1. While a laptop runs a demanding video, hold your hand near (not on) its exhaust vent.
    2. Notice the warm air: that is the electrical power leaving as heat.
    3. Estimate its power from the charger's rating and compare with the airflow formula.

    Safety: Hand near the vent only; never block vents or open the laptop. Stop if anything is hot to touch.

  2. Virtual

    PUE what-ifs

    1. In the demonstration, keep the IT load fixed.
    2. Lower the PUE from 1.6 to 1.2 and record the yearly saving in MWh.
    3. Explain where the saved energy was going.

    Safety: Runs entirely in your browser.