Intelligent Greenhouse

Keep the seedlings alive through a cold night, on a budget.

Seedlings in a small glass greenhouse need 18–26 °C. Outside it falls to 1 °C before dawn, a vent opens at 22:00, the thermometer is noisy and electricity costs money. Design the sensing, the decisions and the actuators, then prove your design works.

What you will learn to do

  1. 1Trace the feedback loop: measure → compare → decide → act → the world changes → measure again.
  2. 2Explain why a greenhouse warms and cools exponentially, and estimate its time constant τ = C/UA.
  3. 3Use hysteresis to stop a noisy sensor making a relay chatter, and count the cost in switch events.
  4. 4Program a Bench-8 processor as an embedded thermostat that meets a numerical specification.
  5. 5Tune on/off, P and PI control and explain the trade-off between energy, comfort and actuator wear.
  6. 6Compare two designs fairly with seeded repeated trials (mean ± standard deviation) and state the model's limits.

Five ways in

  • Level 1 · Explorer · Cause and effectFind the smallest heater dial setting that keeps the seedlings at or above 18 °C all night.
  • Level 2 · Builder · Rules and debuggingDebug the rule so the greenhouse never drops below 18 °C and the heater switches no more than 100 times all night.
  • Level 3 · Innovator · Integration to a specificationMake the Bench-8 thermostat meet the full specification: never below 18 °C, never above 26 °C, at most 25 kWh and at most 100 heater switches.
  • Level 4 · Systems Engineer · Dynamics and trade-offsTune the system to stay within 18–26 °C for 24 hours using at most 14 kWh, with as few actuator switch events as you can.
  • Level 5 · Research Engineer · Evidence under uncertaintyDecide, with evidence, whether a PI controller beats a well-set thermostat on energy and switch events for this greenhouse, at equal comfort.

Workspace

Pick a mode, read the brief, then run, measure and improve. Automatic feedback appears after each run. Nothing leaves your device unless you save to your Journal or export.

Loading the Nexus workspace…

Where this connects in the School

Limits of the model

A simplified educational model. Knowing what it leaves out is part of the project.

  • One well-mixed air volume: real greenhouses have warm roofs, cold floors and draughts.
  • Illustrative constants (C = 0.6 MJ/K, UA = 100 W/K), not measured from a real greenhouse.
  • A fixed, cloudless weather pattern; real nights vary and wind changes the heat loss.
  • No humidity, condensation, plant transpiration or soil heat storage beyond C.
  • Actuators respond instantly (except the vent motor's travel time); the heater has no warm-up lag.
  • Energy is counted at the meter; no tariff, carbon intensity or equipment cost.

Supported components

Greenhouse · Temperature sensor · Moving average · Comparator · Schmitt trigger · Relay driver · Logic gate · NOT · On/off controller · P controller · PI controller · Bench-8 processor · Heater · Fan · Vent motor · Schedule · Step · Recorded profile · Meter · Plot channel · Event log · Gain · Sum · Unit converter · Unit delay