Lite / Engineering Complex Systems / Week 12
Read the plant from its step response
You're handed a heater you've never seen. One five-minute test is enough to model it. Which test, and what do you read off?
Why should I care?
Real plants don't come with τ printed on the side. A step test, apply a known input change and log the output, is the quickest way to get a model good enough to start tuning a controller. It is one of the most common tests in industry.
- Estimate K and τ from a measured step response using the final value and the 63 % crossing.
- Compute τ from any single reading with τ = −t/ln(1 − y/y∞).
- Explain how measurement noise limits the accuracy of a step-test estimate.
Predict
A step test levels off at 50 °C above start, and at t = 3 min it was 31.6 °C above start. What is τ?
- About 1.5 min
- About 3 min
- About 6 min
- Can't tell without more data
Guess first, then reveal
31.6/50 = 0.632, the 63 % point, so τ ≈ 3 min. You can get τ from any reading: τ = −t/ln(1 − y/y∞).
Discover
Switch to Mystery plant mode. For each of the five plants, read the final value from the dots, compute 63 % of it, read off the time and enter your τ. Aim for within 12 %, then press New mystery plant.
What the interactive shows (text version)
In mystery mode the diagram shows noisy measurement dots rising and levelling off. You read the level, take 63 % of it, and read across to the time where the dots cross that height: that time is τ. After checking, the true curve is drawn over the dots.
Understand
The step test
Hold the system steady, then change the input by a known Δu and log the output until it settles. K = Δy∞/Δu, the change in final output per unit input. τ is the time to cover 63 % of Δy∞. If the response has an initial delay before it starts moving, measure τ from when it starts.
Any point will do, some are better
From one reading y at time t: τ = −t / ln(1 − y/y∞). Readings near the start (small y/y∞) and near the end (y/y∞ close to 1) are sensitive to noise, because a small error in y makes a big change in the logarithm. Points between 30 % and 80 % give the most reliable τ.
Use all the data
Better still, fit the whole curve: plot ln(1 − y/y∞) against t. For a true first-order system it is a straight line with slope −1/τ. If it curves, the plant isn't first-order: a second store, a delay or a nonlinearity is showing.
Explain it another way
Intuitive
Like timing how long a bath takes to fill to the overflow: watch it once, and you can predict it next time.
Technical
System identification from step data: K̂ = Δy∞/Δu; τ̂ from the 63.2 % crossing or by least-squares on ln(1 − y/ŷ∞) versus t. Errors in ŷ∞ bias τ̂, so log until clearly settled.
Mathematical
τ = −t/ln(1 − f) with f = y/y∞. Sensitivity: dτ/df = −t/((1 − f)·ln²(1 − f)), which is large as f → 0 or f → 1.
Applied
Process engineers 'bump test' a valve or heater on a real plant: a small, safe step, logged for a few time constants. The resulting K and τ (plus a dead time) feed standard PID tuning rules.
Worked example 1
A 10 % step in fan power changes a room's temperature by 1.8 °C once settled; it reached 1.0 °C after 12 minutes. Find K and τ.
K = 1.8 °C per 10 % = 0.18 °C per %. f = 1.0/1.8 = 0.556, so τ = −12/ln(0.444) = −12/(−0.811) = 14.8 min.
Common mix-ups
You can stop the step test once the output looks nearly flat.
✓ If you underestimate y∞, every τ estimate is biased. Log for at least four or five time constants.
Practice
Practice, not a test. Answers are checked on our server; a wrong answer gets a hint and another try. Nothing is saved.
Apply it
Use the Smart Greenhouse build: apply a heater step and log the air temperature. Estimate K and τ by the 63 % method and by the log-plot method, and compare them.
Reflect
What would you do differently if every step test cost an hour of a real factory's production?