Control systems
Steady-state error
Also called: offset · droop · e_ss · final error
Definition
Steady-state error is the error that remains after the response has settled and stopped changing.
Picture it
If holding the output needs a non-zero command, a pure P controller can only produce it while some error remains. Integral action, a large loop gain or feedforward of the expected command removes or shrinks it.
The maths
e_ss = r − y(∞) first-order plant, P control: e_ss = r / (1 + K Kp)
| Quantity | Unit | Symbol |
|---|---|---|
| ratio | dimensionless | 1 |
Worked example
A heater loop under P control settles at 22.5 °C with a 24 °C setpoint. What is the steady-state error as a percentage of the setpoint?
- e_ss = 24 − 22.5 = 1.5 °C
- 1.5 / 24 × 100 = 6.25 %
Answer1.5 °C, which is 6.25 % of the setpoint.
✓ The 2 numbers in this answer are recomputed from scratch by an automated test.
tune it
PID step response
Simplified model: plant τ·dy/dt = −y + u with τ = 0.5 s and gain 1, forward-Euler steps of 0.01 s, derivative on measurement. Real plants add delay, noise and saturation.
Common misconceptions
- Misconception: Steady-state error is not noise; it is a consistent offset.
- Misconception: A system with an integrator in the plant (such as position from velocity) may have zero steady-state error to a step even with P control.