Skip to content
Tactiverge

Control systems

Steady-state error

Also called: offset · droop · e_ss · final error

Definition

Steady-state error is the error that remains after the response has settled and stopped changing.

Picture it

If holding the output needs a non-zero command, a pure P controller can only produce it while some error remains. Integral action, a large loop gain or feedforward of the expected command removes or shrinks it.

The maths

e_ss = r − y(∞)
first-order plant, P control: e_ss = r / (1 + K Kp)
SI units used in this entry
QuantityUnitSymbol
ratiodimensionless1

Worked example

A heater loop under P control settles at 22.5 °C with a 24 °C setpoint. What is the steady-state error as a percentage of the setpoint?

  1. e_ss = 24 − 22.5 = 1.5 °C
  2. 1.5 / 24 × 100 = 6.25 %

Answer1.5 °C, which is 6.25 % of the setpoint.

✓ The 2 numbers in this answer are recomputed from scratch by an automated test.

tune it

PID step response

Dashed line: setpoint 1. Solid line: output y over 8 s.
Overshoot 0 % · 2 % settling time 5.17 s · final value 0.994

Simplified model: plant τ·dy/dt = −y + u with τ = 0.5 s and gain 1, forward-Euler steps of 0.01 s, derivative on measurement. Real plants add delay, noise and saturation.

Common misconceptions

  • Misconception: Steady-state error is not noise; it is a consistent offset.
  • Misconception: A system with an integrator in the plant (such as position from velocity) may have zero steady-state error to a step even with P control.