Control systems
Proportional control
Also called: P control · Kp · proportional gain
Definition
A proportional controller sets the command to a gain times the error: u = Kp × e. Bigger errors get bigger corrections.
Picture it
It is like steering harder the further you are from the lane centre. Higher gain reacts faster but can overshoot or oscillate. On plants that need a steady push to hold their value, P control alone always leaves some steady-state error.
The maths
u = Kp × e for a first-order plant of gain K: e_ss = r / (1 + K × Kp)
| Quantity | Unit | Symbol |
|---|---|---|
| ratio | dimensionless | 1 |
Worked example
A first-order plant with gain 1 is under P control with Kp = 4 and setpoint 1. What steady-state value and error result?
- e_ss = 1 / (1 + 4) = 0.2
- y_ss = 1 − 0.2 = 0.8
AnswerThe output settles at 0.8, leaving an error of 0.2 (20 %).
✓ The 2 numbers in this answer are recomputed from scratch by an automated test.
tune it
PID step response
Simplified model: plant τ·dy/dt = −y + u with τ = 0.5 s and gain 1, forward-Euler steps of 0.01 s, derivative on measurement. Real plants add delay, noise and saturation.
Common misconceptions
- Misconception: Turning Kp up to kill steady-state error eventually causes oscillation instead.
- Misconception: Kp has units: command units per error unit, such as % PWM per degree.