School/□ Systems Engineer/Week 13

Under, critical, over

A door closer that slams, one that creeps for ten seconds, and one that shuts perfectly. Same spring. What's different?

About 30 min · 3 goals · Checked by automated tests

1.Why should I care?

Picking a damping ratio is one of the most common design choices in mechanical and control engineering. It trades speed against overshoot, and the right answer depends on what overshoot costs: a spilled coffee, a cracked part, or nothing at all.

  • ◇ Describe the step responses of underdamped, critically damped and overdamped systems.
  • ◇ Explain why critically damped is the fastest response without overshoot.
  • ◇ Choose a damping ratio for a stated design goal.

2.Discover

In the feedback lab, choose the second-order plant with P control at a fixed gain. Try ζ = 0.1, 0.4, 0.7, 1 and 2, and record overshoot and settling time for each in a table. Which ζ gives the shortest settling?

Explorer 02 — Feedback control

Measure, compare, correct

A controller compares the setpoint with what the sensor reports and pushes the plant to close the gap. Tune the gains and watch speed, overshoot and accuracy trade against each other.

OUTPUT y vs SETPOINT r0.00.51.0Ts 1.30sCONTROL EFFORT u0.02.0012345678910TIME (s)
  • Setpoint r = 1
  • Closed-loop output
  • Open loop (u = r/K)
  • ±2 % band
Controller

Gains

2.0
1.5
0.20

Applies the command the model says is right, u = r / K, without ever measuring.

Plant

Plant model

Like motor speed or an oven: τ·ẏ = −y + K·u. K = 1.

1.0 s

Real-world effects

0.000

Noise only affects the closed loop: the derivative term amplifies it.

Rise 10–90 %
0.72 s
Overshoot
0.0 %
Settling 2 %
1.30 s
Steady-state err
0.333
theory r/(1+Kp·K) = 0.333

State

P control, Kp 2.0 on a first-order plant with τ 1.0 s. Rise time 0.72 s, overshoot 0.0 %, 2 % settling 1.30 s, steady-state error 0.333 (theory for P: 0.333). Peak control effort 2.00. Open loop: steady-state error 0.000.

P control, Kp 2.0 on a first-order plant with τ 1.0 s. Rise time 0.72 s, overshoot 0.0 %, 2 % settling 1.30 s, steady-state error 0.333 (theory for P: 0.333). Peak control effort 2.00. Open loop: steady-state error 0.000.

How to read this

The top panel shows the setpoint (dashed line at 1) and the plant's true output after a step command at t = 0. The solid line is the controlled system; the dotted line is open loop. The bottom panel shows the control effort u the actuator is asked to deliver.

Rise time is how long the output takes to go from 10 % to 90 % of where it ends up. Overshoot is how far it passes that value. Settling time is when it stays inside ±2 % for good. Steady-state error is the gap left at the end: P control always leaves one on these plants; integral action removes it.

Assumptions & limitations
  • Linear plant models with known, constant parameters (K = 1). Real motors and heaters have friction, dead zones and parameters that drift with temperature and wear.
  • Controller runs every 10 ms and holds its output between samples; the plant is integrated with 4th-order Runge–Kutta at the same step. There is no transport delay, which real systems almost always have.
  • The derivative acts on the measurement (not the error) through a 50 ms low-pass filter, a common practical choice that avoids a spike when the setpoint jumps.
  • Sensor noise is white Gaussian and seeded for repeatability; it is added only to the measurement, never to the true output.
  • Metrics are computed on the true output up to the disturbance time (or 10 s); a response still moving at the end of the window is reported as not settled.
  • Open loop uses the exact plant gain to pick its command. That flatters it: any modelling error would show up as steady-state error.
Can't use the interactive? Read a description instead

In the feedback lab with a second-order plant, a damping ratio of 0.1 gives a large overshoot and long ringing; 0.4 gives moderate overshoot; 0.7 gives a small overshoot and the quickest settling; 1 rises without overshoot; 2 rises slowly without overshoot.

3.Checkpoint: guided practice

Check what you just discovered before going on. Hints appear after a wrong answer.

Practice 1

m = 1 kg, k = 16 N/m, c = 8 N·s/m. Which regime?

4.Predict

Which reaches within 2 % of its final value first after a step?

Guess first. Being wrong here is how the surprise works.

5.Understand

Underdamped (ζ < 1)

The response overshoots, then oscillates with frequency ωd = ωn√(1 − ζ²) inside an exponentially shrinking envelope e^(−ζωn t). Small ζ: big overshoot, long ringing. It rises fastest, which is why lightly damped systems feel 'snappy'.

Critically damped (ζ = 1)

The response x(t) = 1 − (1 + ωn t)·e^(−ωn t) rises without any overshoot and is the fastest response that never crosses the final value. It is the boundary between oscillating and not.

Overdamped (ζ > 1)

Two real time constants. The slower one dominates, and it gets slower as ζ grows: for large ζ it is roughly 2ζ/ωn. No overshoot, but sluggish. A door closer that takes ten seconds is badly overdamped.

Choosing ζ

If overshoot is dangerous (a robot gripper closing on an egg, a lift levelling at a floor), choose ζ close to 1. If a little overshoot is fine and speed matters, ζ ≈ 0.5–0.7 is common: 0.7 gives about 4.6 % overshoot and close to the shortest 2 % settling time.

Explain it another way

Underdamped is a kid on a trampoline, critically damped is a gymnast sticking the landing, overdamped is someone sinking into a beanbag.

Worked example 1

A gripper must close on an egg and never overshoot the target position. Should you choose ζ = 0.5 or ζ = 1.1?

ζ = 1.1. ζ = 0.5 overshoots by about 16 %, squeezing past the target. Slightly over 1 gives margin: if the real mass or friction differs a little, it still won't overshoot.

Common mix-ups

  • Critically damped means 'damped just enough to stop it breaking'.
    ✓ It is a precise mathematical boundary, ζ = 1, between oscillating and non-oscillating responses.

6.Practice on your own

Practice, not a test. Wrong answers get a hint and another try.

Practice 2

Which damping ratio gives the fastest step response that never overshoots?

Practice 3 · a fresh version every time

A mass–spring–damper has m = 1 kg, c = 40 N·s/m and k = 400 N/m. What is its damping ratio ζ? (No unit.)

Practice 4 · a fresh version every time

An underdamped second-order system has damping ratio ζ = 0.37. What percent overshoot does its step response have?

%

Practice 5

Overshoot would crack the part being handled. The best design choice is…

7.Apply it

Write a design note (half a page) for three products of your choice, choosing a target ζ for each and explaining what overshoot would cost and what slowness would cost.

8.Reflect

Concepts: Second-order systems: natural frequency and damping ratio · Derivative action and damping