I removes the error, D adds the damping

P gets you close. Which two extra terms get you exactly there, smoothly, and what does each cost?

About 35 min · 3 goals · Checked by automated tests · Full interactive version

Why should I care?

PID controllers run a huge share of industrial loops. Each term solves one problem and creates another. Knowing the trade-offs is what turns random slider-pushing into engineering.

Predict

You add integral action to a P loop with a steady error. What happens to the steady error?

  1. It shrinks but stays
  2. It goes to zero
  3. It doubles
  4. It oscillates forever
Guess first, then reveal

It goes to zero. While any error remains, the integral keeps growing, raising the command, until the error is exactly zero. The cost is usually some extra overshoot.

Discover

Set the actuator limit to None. Start with P (Kp = 4): note the steady error. Switch to PI and raise Ki from 0 until the error disappears; note the overshoot. Then switch to PID and raise Kd: what happens to overshoot?

What the interactive shows (text version)

In the PID tuner with no actuator limit, P control alone settles below the set point. PI removes that error but adds overshoot. Adding derivative action with PID reduces the overshoot.

You can also open the interactive on the full site when you have a faster connection.

Watch (optional)

Watch for: Listen for which problem each of P, I and D is introduced to solve.

Shows how proportional, integral and derivative terms each help a system reach its setpoint quickly without overshooting or drifting.

“What Is PID Control? | Understanding PID Control, Part 1” by MATLAB (opens YouTube; streaming video uses a lot of data)

The video is optional. Everything you need is in this lesson's text.

Understand

Integral: memory of past error

u = Kp·e + Ki·∫e dt. The integral keeps adding up error, so the command keeps changing until e = 0. At steady state the integral alone supplies the command the plant needs. That is why PI removes steady-state error for steps and constant loads.

Derivative: brakes before the target

Kd·de/dt reacts to how fast the error is shrinking. As the output races towards the set point, D pushes back, like a damper. Many implementations differentiate the measurement, not the error, to avoid a 'kick' when the set point jumps.

The costs

Too much I: slow wobbles and overshoot, and windup when the actuator saturates (next lesson). Too much D: it amplifies sensor noise, because noise changes fast. Real D terms include a low-pass filter. P sets the basic stiffness; I and D trim accuracy and damping.

Explain it another way

Intuitive

P looks at the present, I remembers the past, D predicts the future.

Technical

C(s) = Kp + Ki/s + Kd·s/(T_f·s + 1). The integrator adds a pole at s = 0, making the loop type 1 (zero step error). The filtered derivative adds phase lead up to about 1/T_f.

Mathematical

At steady state with PI: dy/dt = 0 and d(∫e)/dt = e must be 0, so e∞ = 0 regardless of K, Kp or a constant load d.

Applied

3D printer hot ends and drone attitude loops use PID. Temperature loops often use little or no D because temperature sensors are noisy and the process is slow.

Worked example 1

PI controller, Kp = 2, Ki = 1, plant K = 1. At steady state with set point 1, what is the integral value?

e = 0, so u = Ki·∫e = 1 × ∫e. The plant needs u = y/K = 1, so ∫e = 1. The integral has stored exactly the command the plant needs.

Common mix-ups

Practice

Practice, not a test. Answers are checked on our server; a wrong answer gets a hint and another try. Nothing is saved.

Practice 1. What does integral action remove that P alone cannot?
Practice 2. Why is derivative action sensitive to sensor noise?
Practice 3. Why do many PID implementations differentiate the measurement instead of the error?

%

Apply it

Make a three-row table (P, I, D) with columns 'raises', 'lowers', 'risk'. Fill it from your own experiments in the PID tuner, not from memory, and note the settings you used.

Reflect

Which PID term would you add first to a noisy temperature loop, and which would you leave out?