A single guard switch can stick 'closed' while the guard is open. How do you design logic that one broken sensor cannot fool?

About 45 min · 3 goals · Checked by automated tests · Full interactive version

Why should I care?

This is the term project. You will specify, design and verify a small digital system the way engineers do for real machines: words, then a truth table, then logic, then exhaustive tests, then an honest list of what it does not protect against.

Predict

The machine may run only if two independent guard sensors (A, B) both say 'closed', the operator is present (C) and there is no fault (D = 1 means fault). On how many of the 16 input rows should it run?

  1. 1
  2. 4
  3. 8
  4. 15
Guess first, then reveal

Just one: A = 1, B = 1, C = 1, D = 0. Every other combination must keep the machine stopped. Y = A · B · C · ¬D.

Discover

Type A · B · C · ¬D (A, B = guard sensors, C = operator present, D = fault). Read the 16-row truth table and find the single row where Y = 1. Now imagine sensor A is stuck at 1: toggle B to 0 (guard really open) and confirm Y stays 0. Try the same for each other input.

What the interactive shows (text version)

In the expression explorer, Y = A · B · C · ¬D gives a 16-row truth table with Y = 1 only on row 1110: both guard sensors closed, operator present, no fault. If sensor A is stuck at 1 while the guard is open (B = 0), Y stays 0.

You can also open the interactive on the full site when you have a faster connection.

Understand

Specify before you build

Write each signal with its meaning: A = 1 'guard sensor 1 reads closed', B = 1 'guard sensor 2 reads closed', C = 1 'operator present', D = 1 'fault reported'. Then write the rule in one sentence and as a full truth table. Every one of the 16 rows must have a defined output.

Redundancy against a stuck sensor

With one guard sensor, a switch stuck at 1 would let the machine start with the guard open. With two independent sensors both required (A · B), one stuck sensor is not enough: the other still reads 0 and holds the machine off. This is the simplest form of fault tolerance.

Know the limits

The rule Y = A · B · C · ¬D does not detect that a sensor has failed; it only refuses to run on a single false 'safe'. A fault line stuck at 0, or two failures at once, could still fool it. Real safety systems add self-tests and certified hardware. Say so in your design note.

Explain it another way

Intuitive

Two locks on a door, with different keys: losing one key, or one lock jamming open, still leaves the door locked.

Technical

Requiring agreement of redundant channels (1-out-of-2 to stop, 2-out-of-2 to run) means no single channel failing in the 'safe' direction can enable the output. Detecting the failure needs comparison of the channels over time, which needs memory (sequential logic, next year).

Mathematical

Four inputs give 2⁴ = 16 rows. Y = A·B·C·¬D is a single minterm (row 1110), so it is already minimal: 4 literals, one 4-input AND with one input inverted.

Applied

Industrial machine guards often use two switches of different types, and their safety controllers compare the two channels and lock out if they disagree.

Worked example 1

Sensor B is stuck at 1. The guard is actually open, so sensor A reads 0. The operator is present and there is no fault. What is Y?

Y = A · B · C · ¬D = 0 · 1 · 1 · 1 = 0. The healthy sensor A keeps the machine stopped.

Common mix-ups

Practice

Practice, not a test. Answers are checked on our server; a wrong answer gets a hint and another try. Nothing is saved.

rows

rows

Practice 3. Guard sensor A is stuck at 1 and the guard is open (B = 0). C = 1, D = 0. The machine…
Practice 4. Which failure can Y = A · B · C · ¬D NOT protect against on its own?

rows

Apply it

Write your project specification: signal table with meanings, the rule in one sentence, the full 16-row truth table, the simplified expression and a list of at least three failure cases with what your logic does in each. Mark any case it does not handle.

Reflect

Which row of your truth table would you most want a second engineer to check, and why?

Write your answer on paper or in your own notes. Lite never stores what you write.