□ Control systems · feedback loops
PID step response
Simulate a PID controller driving a first-order system and see why integral action removes steady-state error.
- Level 4 · Systems Engineer
- 6 tests
- technically checked
Your task
A heater, a motor and a drone's height all behave roughly like a first-order system: dy/dt = (u − y) / τ, where u is the controller's output.
A PID controller computes u from the error e = setpoint − y: u = kp·e + ki·∫e dt + kd·de/dt
Write pidStep(kp, ki, kd, setpoint, tau, dt, steps) returning steps + 1 outputs, starting at y = 0. Each step, in this order:
- e = setpoint − y
- integral += e × dt
- derivative = (e − prevError) / dt, where prevError starts as the first error (no 'kick'), then prevError = e
- u = kp·e + ki·integral + kd·derivative
- y = y + dt × (u − y) / τ, and push y
Also write finalOutput(kp, ki, kd): the last value of pidStep(kp, ki, kd, 1, 1, 0.05, 400).
Hints (0 of 3 shown)
What gets checked
- pidStep(2, 0, 0, 1, 1, 0.1, 3) → [0, 0.2, 0.34, 0.438]
- finalOutput(2, 0, 0) → ≈ 0.6667 (± 0.001)
Plus 4 hidden tests for edge cases. They run in the sandbox like the others; only the result is shown.