Control systems
Saturation and integrator windup
Real actuators have limits: a motor driver cannot deliver more than full voltage, however large the controller's output. When the command exceeds that limit, the actuator saturates. If the controller has integral action, the integral keeps growing during saturation even though the extra effort has no effect. When the error finally changes sign, this stored-up integral takes time to unwind, causing a large overshoot. This is called integrator windup. Common fixes include clamping the integral or pausing integration while the output is saturated.
Why it mattersWithout windup protection, a robot joint that was blocked for a moment can swing well past its target once it is released.